Product Overview:
The JDZ-3/6/10Q series voltage transformers are suitable for power systems with a rated frequency of 50Hz or 60Hz and a rated voltage of 3kV to 10kV. They are mainly used for energy metering, voltage monitoring, and relay protection
.
Technical parameters:
Rated primary voltage: 10kV.
Rated secondary voltage: 100V.
Accuracy levels include 0.2 and 0.5, with rated outputs ranging from 15VA to 30VA and limit outputs ranging from 200VA to 400VA. The rated insulation levels are 7.2/32/60kV and 12/42/75kV
.
Normal usage conditions:
Installation location: Indoor.
Environmental temperature: maximum+40 ºC; Minimum -5 ºC.
Altitude: not exceeding 1000m.
Atmospheric conditions: There is no severe pollution in the atmosphere
.
Structure and characteristics:
This type of transformer is a semi cast iron core with an outer core. The primary winding is led out at both ends and equipped with a terminal block, which can be used to connect high-voltage wires
.
The winding of the transformer is an epoxy resin fully vacuum cast fully insulated structure, and the iron core is made of high-quality silicon steel sheets stacked together. The product has a small volume and light weight, and installation only occupies limited space
.
Appearance and installation dimensions:
Specific exterior drawings and installation dimensions can refer to the information provided by the manufacturer or product manual
General
This type of transformer adopts an integral casting structure, is applicable for power systems of rated frequency 50Hz or 60Hz and rated voltage up to and including 0.66kV, used for current measurement, electric energy metering, relay protection, etc.
It complies with the standard Q/GDW1572-2014 Technical specification of a low-voltage current transformer for metering.
Use environment
- Altitude: should not exceed 1000m
- Ambient temperature:-5ºC~+40ºC
- Air relative humidity:≤85%
- Air relative site: indoor.
Technical parameter
- Rated secondary current: 5A or 1A
- Power factor: cosφ=0.8(lag)
- Rated frequency: 50Hz or 60Hz
- Rated primary current, rated output, and accurate level see table 1
- Insulating property: primary winding to secondary winding and ground, and secondary winding to the ground can bear the power frequency withstand voltage 3kV for 1min.
Type |
Rated Current ratio(A) |
Mongline rated secondary output(VA) |
Twin coil rated secondary output(VA) |
0.2S |
0.2 |
0.5 |
10P10 |
0.5 |
10P10 |
LSY3-10/107 |
75/5 |
/ |
/ |
1 |
/ |
1 |
/ |
100/5 |
/ |
/ |
2.5 |
/ |
1 |
/ |
150/5 |
/ |
/ |
2.5 |
2.5 |
1.5 |
/ |
200/5 |
/ |
2.5 |
2.5 |
5 |
2.5 |
5 |
300/5 |
2.5 |
2.5 |
5 |
5 |
2.5 |
5 |
400/5 |
5 |
5 |
5 |
7.5 |
5 |
7.5 |
500/5 |
5 |
5 |
10 |
10 |
5 |
10 |
600/5 |
5 |
10 |
10 |
10 |
5 |
10 |
800/5 |
10 |
10 |
10 |
10 |
5 |
10 |
Overall dimension drawing