DAHU electrical specializes in the production of 0.5-40.5kv transformers. It has cooperated with many national power bureaus for 10 years and exported to foreign markets. If there is any quality problem within the warranty period, it can be replaced free of charge.

LZZBJ9-10A current transformer is an indoor epoxy resin casting pillar type full working condition type product, suitable for current and power measurement and relay protection in 10kV and below power system. The following is the key information of this product:
Product Overview:
LZZBJ9-10A type current transformer is suitable for power systems with rated frequency of 50Hz or 60Hz and rated voltage of 10kV
.
Model Meaning:
The "L" in the model stands for current transformer, "Z" stands for pillar type, "Z" stands for cast insulation, "B Z" stands for pillar type, 'Z' stands for cast insulation, 'B' stands for fully enclosed, 'J' stands for increased capacity or protection level, '9' stands for design serial number, '10' stands for rated voltage 10kV.
.
Normal use conditions:
Installation place: indoor.
Ambient temperature: Maximum 40ºC, minimum -5ºC, average daily not more than 30ºC.
Altitude: not more than 1000m or 1500m.
.
Atmospheric conditions: the atmosphere is free of filth and aggressive and explosive media that seriously affect the insulation performance of the transformer.
Atmospheric conditions
Technical parameters:
Rated primary current: from 5A to 1000A, accurate level and combination of 10/15 or 15/15.
Rated secondary current: 5A or 1A.
Insulation level: 12/42/75kV.
Rated output: from 0.45VA to 125VA according to different combinations of accuracy levels.
.
Rated short-time thermal current and rated dynamic stabilizing current: depending on the different rated primary currents, these values vary from 90I1n/1s to 225I1n.
.
Structural features:
This type of transformer is epoxy resin casting fully closed structure, with excellent insulation properties and moisture resistance. Compact structure, small volume, light weight and easy surface cleaning. The secondary wiring is equipped with a junction box, and there are four mounting holes on the bottom plate for installation.
Installation and Maintenance.
Installation and maintenance:
The transformer arrives at the use of units need to check the packing list should be attached to the packing box, product certification, instruction manual and factory certificate of conformity. The structure of the product has no defects or damage caused by transportation or other reasons. The grounding bolt should be properly grounded before the transformer is used. During operation, the secondary winding must be reliably connected to the load, and the unused secondary winding must be shorted to the secondary outlet terminal.
The secondary winding must be connected to the load reliably during operation.
The above information provides a detailed description of the LZZBJ9-10A current transformer, including its overview, model meaning, normal conditions of use, technical parameters, structural features, as well as installation and maintenance requirements.